Problem  | Cause  | Resolution  | 
Only one system is visible in the Views list box of the System Browser, even if the distributed environment is configured using SMC.  | - No time synchronization between the distributed systems.
    | - Align the computer clocks of the distributed systems using the Date and Time settings from the Control Panel of your computer.
    | 
Not able to log into the Partner system in distribution after changing the System Name or System ID.  | - System name and/or System ID of the project in distribution are changed.
    | - Stop all systems in distribution.
 - Delete cashed identification container files (with extension *.bin on Server) on all systems in distribution at the path 
 [installation drive:]\[installation folder]\[project name]\data. - Start the systems.
 - Manually change graphics references, macros and so on from all partner systems.
    | 
Binding/security mismatch between sender and receiver error displays when: - you try to synch the distribution between systems in distribution or  - access Server system from Client in the Client/ Server setup or  - access Server system from the remote web server (IIS) hosted on Client/FEP system.  | - GMS SMC Project Data Service is not started in the Services expander on the Server or 
 is not accessible from the distribution partner/client/remote web (IIS) server system.    | - Check if GMS SMC Project Data Service is started in the Services expander. If not, then start the service manually.
 - Next, check if you are able to access the URL 
 http://localhost:8888/SiemensGmsSmcProjectDataService  from Partner system in distribution or Client or remote web server (IIS) machine. - Check machine and port of GMS SMC Project Data Service both are accessible from the Partner/Client/remote web server (IIS) machine and check that the firewall is not blocking the service port.
    |