 - Engineering Step-by-Step
 - Subsystem Integration
 - APOGEE BACnet
 - Working with APOGEE BACnet Applications
 - APOGEE FLN Device Commander
 - Setting the Initial Value for a BACnet Subpoint
 
Setting the Initial Value for a BACnet Subpoint
- You want to set the initial value of a subpoint that appears across multiple devices and applications.
 
- You want to command the initial value for one or more BACnet subpoints. 
 
- System Manager is in Engineering mode and you have selected the FLN Device Commander tab.
 
- In System Browser, select Management View.
 
- Select Project > Field Networks and then navigate to a network, panel, or device, or drag-and-drop multiple devices into the Selected TECs pane. 
 
- The FLN devices and their children from the network, panel, or device display in the Selected TECs pane in the FLN Device Commander tab.
 
- From the Application drop-down menu, select the application number whose subpoints initial value you want to set. 
 
- In the Applicable TEC pane, the devices associated with the application display.
 
- From the Subpoint drop-down menu, select the subpoint whose initial value you want to change.
 
- Select the Set Initial Value radial button, to change the initial value of the BACnet subpoint.
 
- In the Value field, type the desired initial value.
 
- Click the Execute button.
 
- (Optional) Click View Log to view and save the devices and subpoint status.
 
- Click Close.
 
- The Command Results displays a log of point commands that were issued since the last time the log was cleared.
 