Option 2 – Enable Events for Individual IEE Occupancy Tool Zones
Use this method to modify an alarm configuration for individual IEE Occupancy zones.
- Select the IEE Occupancy Tool zone for which you want to enable alarm. For example: Project > Field Networks > [IEE Occupancy Tool Network] > [Zone]. 
NOTE: You can also use CTRL or SHIFT to make a multiple selection, for example of two or more zones to which you want to apply the same modification. 
- In the Object Configurator tab, close the Main expander and open the Properties expander.
 
- In the list on the left, select the Property for which you want to enable the event. For example: CurrentOccupancy, NumberOfEntries, NumberOfExits.
 
- The Details, Alarm Configuration and other expanders on the right update to show the settings of the selected property.
 
- In the Alarm Configuration expander: 
a. Set the Valid field so it displays a gray (not blue) checkmark.
b. Select the Alarm config.activated check box. 
- Click Save 
. 
- The modified alarm configuration will apply to the selected IEE Occupancy Tool zones.
 
