 - Engineering Step-by-Step
 - Subsystem Integration
 - Honeywell Esser
 - Integrating the Esser Fire System Through Offline Configuration
 - Set Read Property and Polling Rate
 
Set Read Property and Polling Rate
- Under [BACnet network] > Hardware, select the device.
 
- Open the Other Settings expander, and select the following check boxes:
 
- Use only read property
NOTE: This setting is required for third-party devices that do not support RPM. 
- Disallow Subscriptions 
NOTE: This setting is required to use only the Read property service for all subscriptions. 
- Open the COV and Polling Info expander, and in the Polling rate field, decrease the value to the minimum (that is, 5 seconds).
 
- Click Save 
.