Configure STT20 Fire Panels in the Cerloop
Repeat this procedure for all the STT20 panels you want to add.
- Select Project > Field Networks > [BACnet Network] > [Cerloop].
 
- In the Cerloop tab, click New 
 and select New STT20. 
- In the New Object dialog box, enter a name and description.
 
- Click OK.
 
- The newly created STT20 is automatically selected in System Browser.
 
- In the Configuration expander, enter the following parameters:
 
- Instance number: the BACnet Device Identifier.
 
- Local address: STT20 address in the Cerloop. Valid values are: 111 to 118, 121 to 128, 131 to 138, 141 to 148, 211 to 218, 221 to 228, 231 to 238 , 241 to 248 (default: 111). 
NOTE: The Local Address must match the value set in the configuration file of the fire system. 
- Click Save 
. 