 - Engineering Step-by-Step
 - Connectivity
 - BACnet
 - BACnet Driver
 - Configuring Time Synchronization
 
Configuring Time Synchronization
- System Manager is in Engineering mode.
 
- In System Browser, select Management View.
 
- Depending on where the BACnet Driver is located (Desigo CC server or FEP station), select one of the following:
 
- Project > Management System > Servers > Main Server > Drivers > [name of driver]
 
- Project > Management System > FEPs > [FEP station] > Drivers > [name of driver]
 
- Click the BACnet tab.
 
- Expand Time Synchronization.
 
- To synchronize time between devices and the management station, configure the following:
 
- Time sync interval. Set the panel synchronization delay in minutes. Default is 1440 (24 hours).
 
- Align intervals. Select the check box to start the periodic time synchronization on the hour.
 
- Interval offset (minutes). Use the arrows to indicate the amount of time between the time sync interval and the actual time sync. 
 
- Click Save 
.