Troubleshooting
The following table is designed to help you resolve issues while configuring and running the Building X Connector extension.
Problem  | Cause  | Resolution  | 
The Agent Status in SMC for Building X Connector displays Stopped.  | The Building Connect Agent is not running.  | In SMC, select System, and then select the Building X Connector tab. From the Toolbar, click Start.  | 
The Agent Status in SMC for Building X Connector displays Running, Disconnected  | The Building Connect Agent is unable to communicate with Building X.  | Check the network connection. Make sure that you can log into the Building X organization.  | 
The Agent Status in SMC for Building X Connector displays Running, Disconnected  | The site is using a list of acceptable URLs and did not include the URL endpoints required to communicate to Building X.  | Add the URL endpoints to the list of allowed URLs. For more information, see the Desigo CC Cybersecurity Guidelines (A6V11646120).  | 
In Desigo CC, the Operational State property displays Not Ready.  | The Building Connect Agent is not running.  | In the SMC Building X Connector tab, click Start.  | 
In Desigo CC, the Operational State property displays Not Ready.  | The Building Connect Agent ports are misconfigured.  | Make sure configured ports are not conflicting with ports used by other applications on the Desigo CC server.  | 
In Desigo CC, the Operational State property displays Not Ready.  | No Building X Connector user is defined. 
  | In Desigo CC, verify that a user account of the type Software account is defined and then configured in Building X Connector tab, Building X Connector Configuration expander, Software User drop-down.  | 
In Desigo CC, the Operational State property displays Not Ready.  | Unable to register Building X application 
  | Make sure that the Building X site device and application is properly defined in the Building X Devices application.  | 
In Desigo CC, the Operational State property displays Not Ready.  | The application is not installed.  | Make sure you complete all steps in Onboard the Management Station to Building X.  | 
In Desigo CC, the Operational State property displays Not Ready.  | The Desigo CC system account has been changed to use a specific account, and now the system does not have access to Building Connect agent configuration files.  | Give the specific account used as the system account read privilege to the secrets folder, located here:  | 
In Desigo CC, the Building X Data State property displays Data Not Aligned.  | The Desigo CC configuration differs from the current Building X configuration.  | Discover and Upload may be required in Desigo CC from the Building X Connector tab, Building X Preview Selection expander. Click Discover, and then click the Upload button.  | 
In SMC, a previously configured Flex Client URL is not displaying.  | There is a connectivity issue between the Building Connect Agent and Building X.  | Resolve the connectivity issue, and then restart SMC to display the URL. If the URL still does not display, see Accessing Information in The Flex Client.  | 
Alarms and COVs are not being sent to Building X.  | In Desigo CC, the Indications State property is disabled.  | In Extended Operation, locate the Indications State property, and then click Enable.  | 
You do not see alarms in Building X.  | Show is not selected for alarm categories in Event Rights.  | Enable Show for alarm categories you want to view. See Configuring the Building X Connector > Add a Security Group.  | 
