FS92 Fire Network Operating Troubleshooting
This section contains troubleshooting information for FS92 Cerberus Pro fire control panels.
Handle Event Problems in Operating Mode
Problem  | Situation  | Do the following...  | 
Cannot silence events from Desigo CC stations. In the Event List, the silence command icon is missing.   | The silence inhibit has been configured on the panel and is currently active. The silence command is only allowed after a predefined delay.  | 
  | 
All control commands have no effects.  | Network connection is down: all object properties show #COM state and object symbols in graphics display a yellow grid.  | 
  | 
Cannot erase the Client UI missing Event.  | The Client UI Supervision trouble does not automatically disappear due to incompatibility between Desigo CC and FS20 panels with firmware 3.0 and 3.1  | 
  | 