Setting Up Commands in Object Models
In the Models & Functions tab, you can configure commands for the properties of object models. The following procedures provide some examples. For reference information, see Command Configuration Expander.

For a list of available commands, see the Command List section.
Set Up a Boolean Command (Out of Service)
- You want to configure a command on an Out of Service property.
 
- In System Browser, select Project > System Settings > Libraries > [... ] > [object model].
 
- Select the Models & Functions tab.
 
- In the Properties expander, select the Out of Service property.
 
- Open the Command Configuration expander.
 
- Under Dependency 1, select the option Out_of_Service.
 
- Click New.
 
- A new line is added to the table.
 
- Click in the Command column, and from the drop-down list select status BACnetWriteToggleOn.
 
- In the Label column, enter a label for the button, for example, Out of Svc.
 
- In the Out_of_Service column, first select the operand equal sign (=) and then select the option In Service.
 
- Select Alias.
 
- Repeat steps 4 to 7 as per the table below.
 
- The Out of Service property is configured.
 
- The buttons for operation are defined.
 
Command  | Label  | Acked_Transitions  | Alias  | |
BACnetWriteToggleOn  | Out of Service  | =  | In Service  | n/a  | 
BACnetWriteToggleOff  | In Service  | =  | Out of Service  | n/a  | 

Additional dependencies can be defined as needed. In this case, select Dependency 2 and 3 and configure the appropriate response.
Analog Output (Present Value)
- In System Browser, select Project > System Settings > Libraries > [... ] > [analog output object model].
 
- Select the Models & Functions tab.
 
- In the Properties expander, select the Present Value property.
 
- Open the Command Configuration expander.
 
- Under Dependency 1, select Undefined.
 
- Click New.
 
- A new line is added to the table.
 
- In the Command column, select status BACnetAnalogWithPriority.
 
- In the Label column, enter a label, for example, Command for the buttons.
 
- In the Current_priority column, first select the operand and then select the desired options as needed.
 
- Select Alias.
 
- Define the user group (Standard, Event, Advanced, Ownership) used to execute the function.
 
- Repeat steps 3 and 4 as per the table below.
 
- The Present Value property is configured.
 
- The buttons for operation are defined.
 
Command  | Label  | Acked_ Transitions  | Alias  | Group  | Expander  | Combi-ned  | |
BACnetAnalogWithPriority  | Command  | *  | n/a  | n/a  | Standard  | Expander  | 
  | 
BACnetReleaseWithPriority  | Release  | *  | n/a  | n/a  | Standard  | Expander  | 
  | 
Detailed Information on BACnetAnalogWithPriority  | |||||
Parameter  | Label  | Default Value  | Value  | Control  | Affected property  | 
Value  | Value  | Runtime  | [x]  | Numeric  | Present_Value  | 
Priority  | Priority  | Provided  | MO =8  | DropDown  | Undefined  | 