Configuring Non-default Device Symbols in Graphics
Scenario
You want to configure a symbol different from the default associated to a device object in graphics.
- You opened a graphic in edit or engineering mode.
- In the Graphic Editor, open the Properties pane.
- In System Browser, select the Manual Navigation check box.
- Select Management View.
- To add a new object, in Field Networks, locate and drag the input device into the graphic.
- The default symbol appears in the graphic.
- Right-click the default symbol and select Symbol Instance > Replace.
- In the list of associated symbols, select one of them. Note the symbols names:
- DYN_3D_WithDISARM… symbols with the disarmed status indication (an X sign on the bottom right)
- DYN_3D_WithADR… symbols with the technical address on top
- DYN_3D_WithDISARM_ADR… symbols with both the disarmed status indication and technical address
- Repeat the procedure from step 3 to configure more symbols as necessary.
- Click Save
to save the graphic.