AlgoRex CS11 System Limits and Compatibility
System Limits
Legacy DMS Connectivity Limits  | |
  | Maximum  | 
NK823x adapter per BACnet network  | 1  | 
Downstream serial connections per NK823x  | 4 (note 1)  | 
Subsystems (CC11, CI11, CK11, STT11, STT20, SI400 Sintony, DF8000) per NK823x  | 50  | 
Subsystems (CC11, CI11, CK11, STT11, FC20, FT20, STT20) per Cerloop via MK7022/NK823x  | 40  | 
C-Bus stations (CT11, CC11, CI11, CK11) per AlgoRex fire system  | 16  | 
CK11 gateways per AlgoRex fire system (8 CC11/CI11 panels per CK11)  | 2  | 
NOTES
- Up to 4 downstream connections per NK823x, on the 5 possible communication lines: the 4 COM ports and the I2C line for DF8000. A configuration including all five connections is not supported.
 
Legacy DMS Connectivity Limits  | |
  | Maximum  | 
Configured objects per NK823x  | 25,000 (note 1)  | 
NOTES
- In DMS configurations, 25,000 configured objects correspond to about 10,000 physical points (detectors, actuators, and so on).
 
CS1140 Compatibility Information
- Compatible panel versions (FW / tool version):
 - EP5, EP5.1
 - EP7F-SR2 (FW 7.39 / AlgoWorks V1.37)
 - EP7F-SR2-Z1 (FW 7.76 / AlgoWorks V1.46)
 - EP7F-SR2-Z2.1 (FW 7.38 / AlgoWorks V1.50)
 - EP7F-SR2-Z2.2 (FW 7.92 & 8.03 / AlgoWorks V1.63)
 - EP7F-SR2-Z3 (FW 8.31 / AlgoWorks 1.92A)
 - EP7F-SR2-Z4 (FW 8.31 / AlgoWorks V1.92A)
 - EP7F-SR3 (FW 8.3x / AlgoWorks V1.94).
 