Configure the DF8000 I/O via COM Port
You can configure DF8000 I/O modules connected to a remote DF8000 CPU unit that communicates to the NK823x unit over a serial line. 
For background information, see DF8000 Reference.
Add the DF8000 with a DF8003 CPU
- In System Browser, select Project > Field Networks > [BACnet network].
 
- Select the Object Configurator tab.
 
- Click New 
 and select New GMS_DF8000_Serial. 
- In the New Object dialog box: 
a. (Optional) Edit the precompiled name and description (DF8000 System via COM Port).
b. Click OK. 
- The new DF8000 System via COM Port object is added and automatically selected in System Browser.
 
- Select the DF8000 tab.
 
- In the Configuration expander, enter the Instance number (the BACnet Device Identifier).
 
- Click Save 
to enable the remaining fields. 
- In the Configuration expander:
 
- Select the communication Baud Rate
 
- Select the Line Type (for COM 1 and COM2: RS232 or RS485)
 
- Select Support CF9003 if you want to connect a CF9003 unit 
NOTE: 19200 bps Baud Rate is not allowed for CF9003 
- Click Save 
. 
- A new DF80003 CPU, with address set to 0, is added to System Browser, and to the Units expander of DF8000 System via COM Port.
 
Add Input / Output Modules to the DF8003 CPU
Repeat this procedure for all the input / output modules connected to the DF8003 CPU. 
NOTE: You cannot mix supervised modules (DF8045 and DF8046) with On/Off modules (DF8020 and DF8040) on the same CPU. Instead, different I/O units can coexist on the same RS485 bus until the maximum addressing limit is reached. See Valid DF8000 I/O Configurations on I2C Bus.
- In System Browser, select Project > Field Networks > [BACnet network] > [DF8000 system via COM Port] > [DF8003 CPU].
 
- Select the DF8000 tab.
 
- Click New 
 and select the type of module you want to add: 
- DF8040 Digital Input Module
 
- DF8020 Relay Output Module
 
- DF8045 Balanced NC Input Module
 
- DF8046 Balanced NO Input Module
 
- In the New Object dialog box: 
a. (Optional) Edit the precompiled name and description.
b. Click OK. 
- The new module is added to System Browser, and to the Modules expander of the DF8003 CPU.
 
- In the Modules expander, select the newly added module.
 
- Enter an Address (1-6) that matches the setting on the hardware module. Be aware that addressing errors are not notified as fault events.
 
- Click Save 
. 
(Optional) Add Other DF8003 CPUs with I/O Module
Do this procedure if the hardware configuration includes additional DF8003 CPUs.
- In System Browser, select Project > Field Networks > [BACnet network] > [DF8000 system via COM Port].
 
- In the DF8000 tab, click New 
. 
- In the New Object dialog box: 
a. (Optional) Edit the precompiled name and description.
b. Click OK. 
- The new DF80003 CPU is added to System Browser, and to the Units expander of DF8000 System via COM Port.
 
- In the Units expander, select the newly created DF8003 CPU.
 
- Enter an Address (0-15) that does not conflict with those already used for other DF8000 CPU units. See Valid DF8000 I/O Configurations on I2C Bus.
 
- Click Save 
. 
- Configure the I/O modules connected to this DF8003 CPU. See Add I/O Modules to the DF8003 CPU, above.
 
Connect the DF8000 to the NK823x COM Port
- In System Browser, depending on the NK823x serial line connection, select one of the following:
Project > Field Networks > [BACnet Network] > [NK823x] > [com port]
Project > Field Networks > [BACnet Network] > [NK823x] > [Expansion Board] > [com port]. 
- Select the NK8000 tab.
 
- In the Configuration expander, from the Control unit drop-down list, select the DF8000 System via COM Port configured above.
 
- Click Save 
. 
