Troubleshooting Schindler elevators
Handling Import Error Conditions
Message | Situation | Do the following… |
| The selected file is an invalid data file, not created with SLV_OPCExplorer.exe. | Create a new CSV export file with SLV_OPCExplorer.exe and attempt to import it. |
| The import did not recognize one of the objects for import. | If you do not know the exact reason for the missing object type, click Abort to stop the import procedure. Alternatively, you can choose to Continue and skip the missing object or click Continue All to ignore any further recoverable errors. In any case, try creating a new XML file and re-importing it. If the problem persists, contact Technical Support. |
| The import function recognized more points than defined on the project. The import is cancelled after confirming the message with OK. | The project is set to Small by default and supports 25,000 data points. Change the project size. NOTE: Only change the project size if your hardware meets the requirements of a larger project. |
| The project size of system data points is nearly reached (current system size + the imported size). | Change the project size to import additional data points. |
The SLV_OPCExplorer Tool Does not Start
Situation | Possible Causes | Do the following… |
The SLV_OPCExplorer Export Tool does not start. | An older version of the OPC Core Components is installed on the computer. | From the Desigo CC distribution media, open folder ..\GMS\Prerequisites\OPC Core Components and reinstall the OPC Core Components Redistributable (x64).msi. |
No Communication with the OPC Server
Situation | Possible Causes | Do the following… |
No communication is available. | The Desigo CC OPC driver has not started. | Start the Desigo CC OPC driver. |
No Communication with the Schindler OPC Server | Softing dataFEED communications has not started. | Right-click NOTE: The state |
No communication, although state | Conflict with Desigo CC drivers and Softing dataFEED drivers. | 1. Stop the Desigo CC OPC driver. 2. Stop Softing dataFEED on both computers. 3. Restart all drivers. |
No online data is displayed. | The import file is not up-to-date. | Create a new export file and import the new data. |