FS92 Fire System Architectures

Desigo CC systems for FS20 fire networks can be configured as a stand-alone management station or client/server network-distributed system.

The possible UL/ULC-complaint configurations are presented in the following examples.

NOTE: No Request/Grant/Deny (RGD) mechanism can occur to exchange control between local management stations. For each ULC-compliant fire network, the control on the fire system is assigned to the management station associated to the local control panel that has the control on the voice system.

Conduits: Local connections must comply with UL 864 9th edition, and specifically to sections 49.3 exception 1 and 51.1.2 f. Copper-based wiring must be enclosed in listed conduits within 20 feet.

 

Stand-Alone Management Station Architecture

In single station systems, the C-WEB/SAFEDLINK fire network is connected to the unique Desigo CC station via the GAP unit. The system station and the FC92x GAP must be within 20 feet of each other, and copper network cables must be mechanically protected by UL 864/ULC S527-compliant conduits.

 

Stand-Alone Station Fire System

 

Units installed in the same room within 20 ft from each other

Ethernet wiring within 20 ft in UL/ULC listed conduits

 

Local Client/Server Management Station Architecture

In local client/server solutions, the same type of connection is implemented on the server station that provides communication services to client stations within the same control room.

Desigo CC stations, the FC92x GAP unit, and the Ethernet switch must be within 20 feet of each other, and copper network cables must be mechanically protected by UL 864/ULC S527-compliant conduits. A listed switch must be used.

 

Local Client/Server Fire System

 

Units installed in the same room within 20 ft from each other

Ethernet wiring within 20 ft in UL/ULC listed conduits

 

Client/Server Management Station Architecture with Multiple Fire Networks

Client/server solutions can also support multiple fire networks connected to the server station over a local UL 864/ULC S527-compliant Ethernet Switch.
See UL/ULC Compliance: SAFEDLINK Network Limits for the maximum number of networks supported.

 

Local Client/Server Multiple Networks Fire System

 

Units installed in the same room within 20 ft from each other

Ethernet wiring within 20 ft in UL/ULC listed conduits

 

Wide Client/Server Management Station Architecture

Larger client/server solutions may include additional remote client stations that may be connected over local Ethernet LAN cables of fiber optic links applying a single (DCLB) or dual (DCLC) fiber connection. An appropriate listed switch must be used. As in the central location, note the rules to follow at the remote station.

 

Wide Client/Server Fire System with a Remote Client Station

 

Units installed in the same room within 20 ft from each other

Ethernet wiring within 20 ft in UL/ULC listed conduits

Ethernet over Fiber optic cable (Single mode or Multi mode), connected in Style4/ Class B or Style7/Class X

 

Wide Client/Server Management Station Architecture with Multiple Fire Networks and FEP Station(s)

Wide client/server solutions can also support multiple FCnet/SAFEDLINK fire networks, both local and remote. A FEP station may be required for balancing the communication workload on the server station (refer to UL/ULC Compliance: SAFEDLINK Network Limits).

 

Wide Client/Server Multiple Networks Fire System

 

Units installed in the same room within 20 ft from each other

Ethernet wiring within 20 ft in UL/ULC listed conduits

Ethernet over Fiber optic cable (Single mode or Multi mode), connected in Style4/ Class B or Style7/Class X

 

Redundant Management Station Servers and FEPs Architecture

A large client/server solution can support redundant sets of stations, including dual servers and dual FEPs. While the main system has full control, the backup system runs with no control of the fire system. If the main system fails, a manual operation on all stations (user account switchover) can transfer the control to the redundant system.

 

Redundant Wide Client/Server Multiple Networks Fire System

 

Units installed in the same room within 20 ft from each other

Ethernet wiring within 20 ft in UL/ULC listed conduits

Ethernet over Fiber optic cable (Single mode or Multi mode), connected in Style4/ Class B or Style7/Class X

 

Distributed Systems Architecture

Very large-size solutions may include multiple local systems in a distributed architecture. Each local system is based on a project, and multiple projects can be deployed to one or more interconnected server computers. Local system projects can include FEPs and local redundant solutions. The client stations can access data from all projects.

 

Distributed Architecture with 2 Systems (A and B) on 2 Corresponding Servers Handling a Total of 4 Fire Networks

 

Units installed in the same room within 20 ft from each other

Ethernet wiring within 20 ft in UL/ULC listed conduits

Ethernet over Fiber optic cable (Single mode or Multi mode), connected in Style4/ Class B or Style7/Class X