FS92 Limits and Compatibility
For system limits relating to the network configuration, see UL/ULC Compliance: SAFEDLINK Network Limits.
Compatibility Information
Panel version: MP2.0
- Panel firmware (FW/BDV): 51.16.0_00 / 51.16.0_01
Panel version: MP2.1
- Panel firmware (FW/BDV): 60.18.00_00 / 60.18.1_02
Panel version: MP2.2
- Panel firmware (FW/BDV): 62.9.0 / X9_62.9.0_03
Panel version: MP3.0
- Panel firmware (FW/BDV): 1-71.24.3_01 / 1-71.24.0_01
Panel version: MP3.1
- Panel firmware (FW/BDV): 1-72.xx.x
Panel version: MP4.0
- Panel firmware (FW/BDV): 1-81.xx.x
Status and Command Propagation in System Browser
In the System Browser views, Desigo CC provides status and command propagation based on the parent-child model along the project hierarchy.
The status of common properties, such as alarm, fault, or technical exclusion, are relayed from source objects of the fire panel up to the top of the view.
Vice versa, the action of common commands is propagated down from high-level objects, where applicable along the hierarchical structure.
Referring to the internal structure of the fire panel, the propagation is implemented as follows:
- The Detection tree propagation is supported to provide all required functionality
- Control, Hardware and Operation trees are not supported, although certain statuses may be propagated
NOTE: Propagation occurs in all trees for objects whose Desigo CC model is common to the Detection tree.