Treating FS92 Fire and Carbon Monoxide (CO) Detection Troubles

Trouble treatment can include multiple steps. The following procedure presents a typical scenario. You can suspend/resume this procedure at any step.

  1. (Optional) Select the event (one at the time).
    NOTE: The next expected command (Acknowledge, Silence, or Reset) is directly available for each event in Event List without any selection.
  1. Click Acknowledge .
  • This informs the local panels that the event treatment is started on the management station.
  1. Depending on the specific situation, start the required counter-measures to address the actual trouble situation in the equipment.
  1. Ensure that the trouble condition has terminated.
  1. Click Reset to reset the alarm.
  1. Click the event button.
  • The event is cleared from Event List.