 - Engineering Step-by-Step
 - Subsystem Integration
 - APOGEE BACnet
 - Integrating APOGEE BACnet Systems
 - (Optional) Manually Configuring APOGEE BACnet
 - Start a BACnet Driver
 
Start a BACnet Driver
- System Manager is in Engineering mode.
 
- You have already added a BACnet driver, and you need to finish configuring and starting it.
 
 
- In System Browser, select Management View.
 
- Depending on where the BACnet Driver is located (Desigo CC server or FEP station), do one of the following:
 
- Select Project > Management System > Servers > Main Server > Drivers
 
- Select Project > Management System > FEPs > [FEP station] > Drivers
 
- Click the BACnet tab (which finishes configuring the BACnet driver).
 
- Click the Extended Operation tab.
 
- In the Manager Status property, click Start.
 
 
- The BACnet driver is now ready to use.